How do AI data centers stay cool, and how much water does that really use?

Written as of · Published · By Robert Scales, with AI tools · 5 min read

Short answer

AI data centers move heat out with liquid running to the chips, then release it through evaporation, which uses water, or through fans and chillers, which use more electricity. The right answer to how much water depends on the site: Google reported one data center using 3.8 billion liters in 2024 and an air-cooled one using 38,000.

Nearly all the electricity a chip uses turns into heat, and a modern AI rack can release about 120 kilowatts of it. The cooling system has one job, which is to carry that heat outside. How it does the job decides whether the site uses a little water or a lot.

Our article on the energy and water behind each AI request covers the cost per prompt. This one looks at the building, because for the people living nearby, the local total matters more than the figure per prompt.

Three ways to get rid of heat

Inside the building, modern AI racks use direct-to-chip liquid cooling, with coolant flowing through plates on the processors. The main difference is what happens to the heat next.

MethodHow it worksWater on siteElectricity
EvaporativeWater is evaporated, as in a cooling tower, and carries the heat awayHighLower
Closed-loop with chillersThe same liquid circulates; machines reject the heat to the airVery low after the first fillHigher
Dry, air-cooledFans blow air across heat exchangersVery lowHigher, especially on hot days

Evaporation is efficient because turning water into vapor absorbs a lot of heat. That water is consumed: it leaves as vapor and does not go back to the local source. A site with a closed loop fills its system during construction and then recirculates it.

What the numbers say

The widely cited totals come from a 2024 Lawrence Berkeley National Laboratory report, as summarized by researchers writing for The Conversation:

United States, 2023Amount
Direct water use for coolingabout 64 billion liters
Indirect water, from generating the electricityabout 800 billion liters
Direct use projected by 2028possibly double or quadruple

So most of the water footprint is usually at the power plant, not the data center. This is why indirect water matters when you compare options, and why company reports that leave it out can look better than they are. The same researchers note that these reports are voluntary and hard to compare.

Single sites vary enormously. Google reported that its data center in Council Bluffs, Iowa, used 3.8 billion liters in 2024, the most of any of its sites, while an air-cooled site in Pflugerville, Texas, used 38,000 liters. The first figure is much bigger than the second, and neither one is the "average" data center.

The trade-off nobody can avoid

Saving water usually costs electricity. Microsoft says so plainly: it began using closed-loop designs for all new data centers in August 2024, saying each would avoid more than 125 million liters a year, and it acknowledges that replacing evaporation with mechanical cooling raises its power usage effectiveness (PUE), the ratio of total facility power to computing power. Its chips can run with warmer coolant, which offsets part of the penalty.

Epoch AI, a research group that tracks AI sites, sees the same pattern in the Stargate project. It reports that at least six of the seven US sites will use closed-loop liquid cooling, chosen in response to public concern about water, and it says this raises costs. It estimates that one Texas site's total power is about 2 gigawatts for 1.4 gigawatts of computing, partly because of the hot climate and closed-loop cooling. Its records for Colossus 2 in Memphis show air-cooled chillers and condensers instead of cooling towers.

More electricity can mean more indirect water and more emissions, depending on what generates it. There is no universally correct choice: a closed loop makes sense where water is scarce and the grid is clean, while the balance may differ in a wet climate with a gas-heavy grid.

A worked example: 100 megawatts

Water efficiency is measured by water usage effectiveness (WUE), in liters per kilowatt-hour of computing energy. In a December 2024 post, Microsoft reported a fleet average of 0.30 L/kWh for its previous fiscal year, and said new designs aim for near zero.

StepCalculationResult
Computing energy in a year100,000 kW × 8,760 hours876 million kWh
Water at fleet average876 million × 0.30 Labout 263 million liters
Water at near-zero designclose to 0 for coolinga small amount, mainly the building's ordinary needs

Illustrative. A real site's WUE depends on climate and design, and this leaves out indirect water. At 2.5 people per household and about 300 liters per person a day, an assumption we chose for illustration, 263 million liters would be about the yearly use of 960 households.

Try it: Find the most recent sustainability report of a large cloud company and look up its WUE. Then check whether it reports water by site, and whether it counts water used to make its electricity.

What should you ask about water when a data center is proposed near you?

Start with what will be evaporated, not what will be withdrawn. Ask which cooling method the site will use, the expected peak-day water use as well as the annual average, and whether the source is drinking water, recycled water or a private well. Peak days matter, since they fall in the hot, dry periods when a local system is already stretched.

Then ask how much extra electricity the design uses and where it comes from, since a dry design can shift the burden to a power plant. Finally, ask whether the figures will be reported publicly once the site is running. Promises made at the permit stage only help if someone can later check them. New York's executive order, for example, asks state regulators to review whether their water withdrawal program fully captures large users, including data centers.

Sources

  1. Next-generation datacenters consume zero water for cooling — Microsoft, December 9, 2024
  2. Data centers consume massive amounts of water — Civil Beat (republished from The Conversation), August 25, 2025
  3. OpenAI Stargate: where the US sites stand — Epoch AI, April 23, 2026

From the Guide to Artificial Intelligence, by Robert Scales, published by Holistic Hybrid Inc. Share and adapt it under CC BY-NC-SA 4.0: credit the guide, link to https://guidetoartificialintelligence.com/en/learn/ai-data-center-water-cooling/, no commercial use without permission, and keep the same licence.

Get the free Guide to Artificial Intelligence

Sign up for the newsletter and receive the free guide: what changed in AI, one lesson, one prompt to try. Unsubscribe in one click.

How we handle your address

Back to top

Display

Your choices are saved in this browser only. No data is sent.

Text size
100%
Colours
Reading
More settings
Accessibility statement

Get the app

Add the guide to your home screen. It opens like an app, and the pages you have read stay available offline.

Read without a connection: download the articles

iPhone and iPad (Safari, Chrome, Edge)

  1. Tap the Share button (the square with an arrow). In Chrome and Edge, it is in the address bar or the menu.
  2. Choose “Add to Home Screen”.
  3. Tap “Add”.

Android (Chrome, Edge, Samsung Internet, Firefox)

  1. Open the browser menu (⋮ or ☰).
  2. Choose “Install app” or “Add to Home screen”.
  3. Confirm with “Install”.

Computer (Chrome, Edge)

  1. Click the install icon at the right end of the address bar, or open the browser menu (⋮ or …).
  2. In Chrome, choose “Cast, save and share”, then “Install page as app”. In Edge, choose “Apps”, then “Install this site as an app”.
  3. Click “Install”.

Mac (Safari)

  1. Open the File menu.
  2. Choose “Add to Dock”.
  3. Click “Add”.

Firefox on a computer can’t install a site as an app. Use Chrome, Edge or Safari instead.